Maintenance
58
840 USE 115 00 Version 1.0
The default is 0.
This is the minimum command. It will displa
the error lo
of the Ethernet web
embedded server module in slot 1 of the controller at Modbus Plus address 49.
.
This will displa
the error lo
of the Ethernet web embedded server module in slot 4
of the controller at Modbus Plus address 49.50. It will displa
debu
information,
use software interrupt 5d and use Modbus Plus adapter number 1. The output will
be redirected to a file named TRACE.OUT.
If
ou have entered a viable command, ERRLOG will respond:
Path DM. x. x. x. x. x was opened
where
x
is the Modbus Plus address of the Quantum controller.
Next, it will list the number and date of the Quantum Ethernet web embedded
server firmware version.
Then, for each entr
in the error lo
, ERRLOG will displa
the followin
information:
Error lo
entr
number.
File name:Line:error code:
The ten re
isters of the microprocessor in hexadecimal
EAX, EDX, ECX,
EBX, EBP, ESI, EDI, ESP, EFLAGS, EIP
.
For hardware exceptions, the file name and line number will be replaced b
the
hardware exception vector number in decimal.
If
ou have re
uested debu
messa
es, ERRLOG will also displa
the Modbus
messa
es and responses between the controller and the PC.
ERRLOG 49 1
Example
ERRLOG 49.50 4 /d /s5d /n1 > TRACE.OUT