The MSTR Instruction
840 USE 115 00 Version 1.0
31
CTE Error Codes
The followin
error codes are returned if there is a problem with the Ethernet
confi
uration extension table
CTE
in
our pro
ram confi
uration.
3.2.4 Read and Write MSTR Operations
An MSTR Write operation
t
pe 1 in the displa
ed re
ister of the top node
transfers data from a master source device to a specified slave destination device
on the network. An MSTR Read operation
t
pe 2 in the displa
ed re
ister of the
top node
transfers data from a specified slave source device to a master
destination device on the network. Read and Write use one data master transaction
path and ma
be completed over multiple scans.
Note:
TCP/IP Ethernet routin
must be accomplished via standard third-part
Ethernet IP router products.
Control Block
Utilization
The re
isters in the MSTR
control block
the top node
contain the Read or Write
information as described in the followin
table:
Hex Error Code Meaning
5047
The MTU is invalid
5048 The hardware len
th is invalid.
5049 The route specified cannot be found.
504A
Collision in select call: these conditions have already been selected by
another task.
504B The task id is invalid.
Hex Error Code Meaning
7001 There is no Ethernet confi
uration extension.
7002 The CTE is not available for access.
7003 The offset is invalid.
7004 The offset + len
th is invalid.
7005 Bad data field in the CTE.
Register Function Content
Displayed Operation Type 1 = Write, 2 = Read.
First Implied Error status Displays a hex value indicatin
an MSTR error.
Exception response, where
response size is incorrect.
Exception code
+ 3000
Exception response where
response size is incorrect.
4001
Read Write