I/O Modules
35013379 02 October 2007 571
Voltmeter
Monitor
Specifications
The following table shows the specifications for the voltmeter monitor for the analog
input/output module.
Common
Specifications
The following table shows the common specifications for the analog input/output
module.
Voltmeter Monitor Specifications
Range 1 ... 5 V (Loop current must be active)
Scaling I
OUT
(mA) x 0.250 = V
OUT
(volts)
Output Impedance 300Ω typical
Maximum Wire Length 1 meter
Common Specifications
Required Addressing 5 Words In 2 Words Out
Bus Current Required (module) 350 mA
Fusing
Internal None required
External User discretion
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com