I/O Modules
35013379 02 October 2007 563
Configuration of the 140AMM09000 Analog Input/Output Module
Overview This section provides information on configuration of the analog input/output module
140AMM09000.
I/O Map Register
Assignment
This module requires five contiguous input (3x) registers and two output (4x)
registers.
3X Registers The following figure shows the 3x registers.
Note: Modsoft V2.2 or above is required to set up your Quantum I/O configuration.
Note: The input data format and resolution are selected in Zoom screen. Voltmeter
mode is recommended for bipolar ranges with signed decimal numbers.
Channel 1 input dataRegister 1
Channel 2 input dataRegister 2
3x Registers
Channel 3 input dataRegister 3
Channel 4 input dataRegister 4
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com