Schneider Automation Modicon Quantum Ethernet Bedienungsanleitung Seite 330

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 382
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 329
Maintenance
330
33002479 06 07/2008
Kernel LED Error The following table describes the Kernel LED errors that may occur and how to
respond to them.
Fault LED The Fault LED will flash briefly following an error as the module attempts to recover.
The following figure shows the Fault LED.
If Then
The Ready LED is on and the Kernel LED is
flashing
The module has detected an invalid software
image.
The Ready LED is on and the Kernel LED is
shining steadily,
An attempt to download a software image has
failed and the module is in kernel mode.
Either of the above conditions exists. Download a new NOE Exec (see
Downloading a New NOE Exec, p. 334).
Fault
Link
ETHERNET TCP/IP
Appl
Active
140
NOE 771 xx
Seitenansicht 329
1 2 ... 325 326 327 328 329 330 331 332 333 334 335 ... 381 382

Kommentare zu diesen Handbüchern

Keine Kommentare